Filtered by vendor Abb
Subscribe
Total
120 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2021-22279 | 1 Abb | 2 Omnicore C30, Omnicore C30 Firmware | 2021-12-17 | 9.3 HIGH | 9.8 CRITICAL |
| A Missing Authentication vulnerability in RobotWare for the OmniCore robot controller allows an attacker to read and modify files on the robot controller if the attacker has access to the Connected Services Gateway Ethernet port. | |||||
| CVE-2019-19107 | 2 Abb, Busch-jaeger | 4 Tg\/s3.2, Tg\/s3.2 Firmware, 6186\/11 and 1 more | 2021-11-03 | 2.1 LOW | 5.5 MEDIUM |
| The Configuration pages in ABB Telephone Gateway TG/S 3.2 and Busch-Jaeger 6186/11 Telefon-Gateway for user profiles and services transfer the password in plaintext (although hidden when displayed). | |||||
| CVE-2019-19104 | 2 Abb, Busch-jaeger | 4 Tg\/s3.2, Tg\/s3.2 Firmware, 6186\/11 and 1 more | 2021-11-03 | 7.5 HIGH | 9.8 CRITICAL |
| The web server in ABB Telephone Gateway TG/S 3.2 and Busch-Jaeger 6186/11 Telefon-Gateway allows access to different endpoints of the application without authenticating by accessing a specific uniform resource locator (URL) , violating the access-control (ACL) rules. This issue allows obtaining sensitive information that may aid in further attacks and privilege escalation. | |||||
| CVE-2019-18250 | 1 Abb | 2 Plant Connect, Power Generation Information Manager | 2021-10-29 | 7.5 HIGH | 9.8 CRITICAL |
| In all versions of ABB Power Generation Information Manager (PGIM) and Plant Connect, the affected product is vulnerable to authentication bypass, which may allow an attacker to remotely bypass authentication and extract credentials from the affected device. | |||||
| CVE-2021-22272 | 2 Abb, Busch-jaeger | 2 Mybuildings, Mybusch-jaeger | 2021-10-08 | 9.0 HIGH | 9.4 CRITICAL |
| The vulnerability origins in the commissioning process where an attacker of the ControlTouch can enter a serial number in a specific way to transfer the device virtually into her/his my.busch-jaeger.de or mybuildings.abb.com profile. A successful attacker can observe and control a ControlTouch remotely under very specific circumstances. The issue is fixed in the cloud side of the system. No firmware update is needed for customer products. If a user wants to understand if (s)he is affected, please read the advisory. This issue affects: ABB and Busch-Jaeger, ControlTouch | |||||
| CVE-2020-24683 | 1 Abb | 2 Symphony \+ Historian, Symphony \+ Operations | 2021-10-07 | 7.5 HIGH | 9.8 CRITICAL |
| The affected versions of S+ Operations (version 2.1 SP1 and earlier) used an approach for user authentication which relies on validation at the client node (client-side authentication). This is not as secure as having the server validate a client application before allowing a connection. Therefore, if the network communication or endpoints for these applications are not protected, unauthorized actors can bypass authentication and make unauthorized connections to the server application. | |||||
| CVE-2020-24680 | 1 Abb | 2 Symphony \+ Historian, Symphony \+ Operations | 2021-10-07 | 4.6 MEDIUM | 7.0 HIGH |
| In S+ Operations and S+ Historian, the passwords of internal users (not Windows Users) are encrypted but improperly stored in a database. | |||||
| CVE-2020-24679 | 1 Abb | 2 Symphony \+ Historian, Symphony \+ Operations | 2021-10-07 | 10.0 HIGH | 9.8 CRITICAL |
| A S+ Operations and S+ Historian service is subject to a DoS by special crafted messages. An attacker might use this flaw to make it crash or even execute arbitrary code on the machine where the service is hosted. | |||||
| CVE-2020-24678 | 1 Abb | 2 Symphony \+ Historian, Symphony \+ Operations | 2021-10-07 | 6.5 MEDIUM | 8.8 HIGH |
| An authenticated user might execute malicious code under the user context and take control of the system. S+ Operations or S+ Historian database is affected by multiple vulnerabilities such as the possibility to allow remote authenticated users to gain high privileges. | |||||
| CVE-2020-24677 | 1 Abb | 2 Symphony \+ Historian, Symphony \+ Operations | 2021-10-07 | 6.5 MEDIUM | 8.8 HIGH |
| Vulnerabilities in the S+ Operations and S+ Historian web applications can lead to a possible code execution and privilege escalation, redirect the user somewhere else or download unwanted data. | |||||
| CVE-2020-24675 | 1 Abb | 2 Symphony \+ Historian, Symphony \+ Operations | 2021-10-07 | 7.5 HIGH | 9.8 CRITICAL |
| In S+ Operations and S+ History, it is possible that an unauthenticated user could inject values to the Operations History server (or standalone S+ History server) and ultimately write values to the controlled process. | |||||
| CVE-2020-24674 | 1 Abb | 2 Symphony \+ Historian, Symphony \+ Operations | 2021-10-07 | 9.0 HIGH | 8.8 HIGH |
| In S+ Operations and S+ Historian, not all client commands correctly check user permission as expected. Authenticated but Unauthorized remote users could execute a Denial-of-Service (DoS) attack, execute arbitrary code, or obtain more privilege than intended on the machines. | |||||
| CVE-2020-24673 | 1 Abb | 2 Symphony \+ Historian, Symphony \+ Operations | 2021-10-07 | 7.5 HIGH | 9.8 CRITICAL |
| In S+ Operations and S+ Historian, a successful SQL injection exploit can read sensitive data from the database, modify database data (Insert/Update/Delete), execute administration operations on the database (such as shutdown the DBMS), recover the content of a given file present on the DBMS file system and in some cases issue commands to the operating system. This can lead to a loss of confidentiality and data integrity or even affect the product behavior and its availability. | |||||
| CVE-2021-22276 | 1 Abb | 10 System Access Point 127v, System Access Point 127v Firmware, System Access Point 2.0 and 7 more | 2021-10-06 | 4.3 MEDIUM | 5.5 MEDIUM |
| The vulnerability allows a successful attacker to bypass the integrity check of FW uploaded to the free@home System Access Point. | |||||
| CVE-2020-24676 | 1 Abb | 2 Symphony \+ Historian, Symphony \+ Operations | 2021-09-14 | 4.6 MEDIUM | 7.8 HIGH |
| In Symphony Plus Operations and Symphony Plus Historian, some services can be vulnerable to privilege escalation attacks. An unprivileged (but authenticated) user could execute arbitrary code and result in privilege escalation, depending on the user that the service runs as. | |||||
| CVE-2020-8481 | 1 Abb | 1 800xa System | 2021-09-14 | 10.0 HIGH | 9.8 CRITICAL |
| For ABB products ABB Ability™ System 800xA and related system extensions versions 5.1, 6.0 and 6.1, Compact HMI versions 5.1 and 6.0, Control Builder Safe 1.0, 1.1 and 2.0, Symphony Plus -S+ Operations 3.0 to 3.2 Symphony Plus -S+ Engineering 1.1 to 2.2, Composer Harmony 5.1, 6.0 and 6.1, Melody Composer 5.3, 6.1/6.2 and SPE for Melody 1.0SPx (Composer 6.3), Harmony OPC Server (HAOPC) Standalone 6.0, 6.1 and 7.0, ABB Ability™ System 800xA/ Advant® OCS Control Builder A 1.3 and 1.4, Advant® OCS AC100 OPC Server 5.1, 6.0 and 6.1, Composer CTK 6.1 and 6.2, AdvaBuild 3.7 SP1 and SP2, OPCServer for MOD 300 (non-800xA) 1.4, OPC Data Link 2.1 and 2.2, Knowledge Manager 8.0, 9.0 and 9.1, Manufacturing Operations Management 1812 and 1909, confidential data is written in an unprotected file. An attacker who successfully exploited this vulnerability could take full control of the computer. | |||||
| CVE-2020-11420 | 2 Abb, Generex | 4 Cs141, Cs141 Firmware, Cs141 and 1 more | 2021-09-14 | 4.0 MEDIUM | 6.5 MEDIUM |
| UPS Adapter CS141 before 1.90 allows Directory Traversal. An attacker with Admin or Engineer login credentials could exploit the vulnerability by manipulating variables that reference files and by doing this achieve access to files and directories outside the web root folder. An attacker may access arbitrary files and directories stored in the file system, but integrity of the files are not jeopardized as attacker have read access rights only. | |||||
| CVE-2019-19106 | 2 Abb, Busch-jaeger | 4 Tg\/s3.2, Tg\/s3.2 Firmware, 6186\/11 and 1 more | 2021-09-14 | 6.4 MEDIUM | 9.1 CRITICAL |
| Improper implementation of Access Control in ABB Telephone Gateway TG/S 3.2 and Busch-Jaeger 6186/11 Telefon-Gateway allows an unauthorized user to access data marked as restricted, such as viewing or editing user profiles and application settings. | |||||
| CVE-2020-24686 | 1 Abb | 12 Pm554, Pm554 Firmware, Pm556 and 9 more | 2021-03-05 | 5.0 MEDIUM | 7.5 HIGH |
| The vulnerabilities can be exploited to cause the web visualization component of the PLC to stop and not respond, leading to genuine users losing remote visibility of the PLC state. If a user attempts to login to the PLC while this vulnerability is exploited, the PLC will show an error state and refuse connections to Automation Builder. The execution of the PLC application is not affected by this vulnerability. This issue affects ABB AC500 V2 products with onboard Ethernet. | |||||
| CVE-2020-24685 | 1 Abb | 3 Ac500 Cpu Firmware, Pm573-eth, Pm583-eth | 2021-02-16 | 5.0 MEDIUM | 8.6 HIGH |
| An unauthenticated specially crafted packet sent by an attacker over the network will cause a denial-of-service (DoS) vulnerability. Vulnerability allows attacker to stop the PLC. After stopping (ERR LED flashing red), physical access to the PLC is required in order to restart the application. This issue affects: ABB AC500 V2 products with onboard Ethernet version 2.8.4 and prior versions. | |||||