Vulnerabilities (CVE)

Filtered by vendor Abb Subscribe
Total 120 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2019-18997 1 Abb 1 Pb610 Panel Builder 600 2020-10-22 5.0 MEDIUM 7.5 HIGH
The HMISimulator component of ABB PB610 Panel Builder 600 uses the readFile/writeFile interface to manipulate the work file. Path configuration in PB610 HMISimulator versions 2.8.0.424 and earlier potentially allows access to files outside of the working directory, thus potentially supporting unauthorized file access.
CVE-2020-10287 1 Abb 4 Irb140, Irb140 Firmware, Irc5 and 1 more 2020-07-24 7.5 HIGH 9.8 CRITICAL
The IRC5 family with UAS service enabled comes by default with credentials that can be found on publicly available manuals. ABB considers this a well documented functionality that helps customer set up however, out of our research, we found multiple production systems running these exact default credentials and consider thereby this an exposure that should be mitigated. Moreover, future deployments should consider that these defaults should be forbidden (user should be forced to change them).
CVE-2020-10288 2 Abb, Windriver 4 Irb140, Irc5, Robotware and 1 more 2020-07-23 7.5 HIGH 9.8 CRITICAL
IRC5 exposes an ftp server (port 21). Upon attempting to gain access you are challenged with a request of username and password, however you can input whatever you like. As long as the field isn't empty it will be accepted.
CVE-2020-8471 1 Abb 3 800xa System, Compact Hmi, Control Builder Safe 2020-06-09 4.6 MEDIUM 7.8 HIGH
For the Central Licensing Server component used in ABB products ABB Ability™ System 800xA and related system extensions versions 5.1, 6.0 and 6.1, Compact HMI versions 5.1 and 6.0, Control Builder Safe 1.0, 1.1 and 2.0, Symphony Plus -S+ Operations 3.0 to 3.2 Symphony Plus -S+ Engineering 1.1 to 2.2, Composer Harmony 5.1, 6.0 and 6.1, Melody Composer 5.3, 6.1/6.2 and SPE for Melody 1.0SPx (Composer 6.3), Harmony OPC Server (HAOPC) Standalone 6.0, 6.1 and 7.0, ABB Ability™ System 800xA/ Advant® OCS Control Builder A 1.3 and 1.4, Advant® OCS AC100 OPC Server 5.1, 6.0 and 6.1, Composer CTK 6.1 and 6.2, AdvaBuild 3.7 SP1 and SP2, OPCServer for MOD 300 (non-800xA) 1.4, OPC Data Link 2.1 and 2.2, Knowledge Manager 8.0, 9.0 and 9.1, Manufacturing Operations Management 1812 and 1909, weak file permissions allow an authenticated attacker to block the license handling, escalate his/her privileges and execute arbitrary code.
CVE-2020-8482 1 Abb 1 Device Library Wizard 2020-06-01 2.1 LOW 5.5 MEDIUM
Insecure storage of sensitive information in ABB Device Library Wizard versions 6.0.X, 6.0.3.1 and 6.0.3.2 allows unauthenticated low privilege user to read file that contains confidential data
CVE-2020-8473 1 Abb 1 800xa Base System 2020-05-14 6.8 MEDIUM 7.8 HIGH
Insufficient folder permissions used by system functions in ABB System 800xA Base (version 6.1 and earlier) allow low privileged users to read, modify, add and delete system and application files. An authenticated attacker who successfully exploit the vulnerabilities could escalate his/her privileges, cause system functions to stop and to corrupt user applications.
CVE-2020-8472 1 Abb 5 Ac800m, Base Software, Control Builder M and 2 more 2020-05-14 6.8 MEDIUM 7.8 HIGH
Insufficient folder permissions used by system functions in ABB System 800xA products OPCServer for AC800M (versions 6.0 and earlier) and Control Builder M Professional, MMSServer for AC800M, Base Software for SoftControl (version 6.1 and earlier) allow low privileged users to read, modify, add and delete system and application files. An authenticated attacker who successfully exploited the vulnerabilities could escalate his/her privileges, cause system functions to stop and to corrupt user applications.
CVE-2020-8478 1 Abb 4 Ac800m, Base Software, Mms Server and 1 more 2020-05-13 2.1 LOW 3.3 LOW
Insufficient protection of the inter-process communication functions in ABB System 800xA products OPC Server for AC 800M, MMS Server for AC 800M and Base Software for SoftControl (all published versions) enables an attacker authenticated on the local system to inject data, affecting the online view of runtime data shown in Control Builder.
CVE-2020-8489 1 Abb 1 800xa Information Management 2020-05-08 4.6 MEDIUM 7.8 HIGH
Insufficient protection of the inter-process communication functions in ABB System 800xA Information Management (all published versions) enables an attacker authenticated on the local system to inject data, affecting the runtime values to be stored in the archive, or making Information Management history services unavailable.
CVE-2020-8488 1 Abb 1 800xa Batch Management 2020-05-08 4.6 MEDIUM 7.8 HIGH
Insufficient protection of the inter-process communication functions in ABB System 800xA Batch Management (all published versions) enables an attacker authenticated on the local system to inject data, affecting User Interface update during batch execution and/or compare/printing functionalities.
CVE-2020-8484 1 Abb 1 800xa 2020-05-08 4.6 MEDIUM 7.8 HIGH
Insufficient protection of the inter-process communication functions in ABB System 800xA for DCI (all published versions) enables an attacker authenticated on the local system to inject data, allowing reads and writes to the controllers or cause windows processes to crash.
CVE-2020-8487 1 Abb 1 800xa Base System 2020-05-08 4.6 MEDIUM 7.8 HIGH
Insufficient protection of the inter-process communication functions in ABB System 800xA Base (all published versions) enables an attacker authenticated on the local system to inject data, affect node redundancy handling.
CVE-2020-8486 1 Abb 1 800xa Rnrp 2020-05-07 4.6 MEDIUM 7.8 HIGH
Insufficient protection of the inter-process communication functions in ABB System 800xA RNRP (all published versions) enables an attacker authenticated on the local system to inject data, affect node redundancy handling.
CVE-2020-8485 1 Abb 1 800xa 2020-05-07 4.6 MEDIUM 7.8 HIGH
Insufficient protection of the inter-process communication functions in ABB System 800xA for MOD 300 (all published versions) enables an attacker authenticated on the local system to inject data, allowing reads and writes to the controllers or cause windows processes to crash.
CVE-2020-8477 1 Abb 1 800xa Information Manager 2020-04-30 6.8 MEDIUM 8.8 HIGH
The installations for ABB System 800xA Information Manager versions 5.1, 6.0 to 6.0.3.2 and 6.1 wrongly contain an auxiliary component. An attacker is able to use this for an XSS-like attack to an authenticated local user, which might lead to execution of arbitrary code.
CVE-2020-8474 1 Abb 1 800xa Base System 2020-04-30 4.6 MEDIUM 7.8 HIGH
Weak Registry permissions in ABB System 800xA Base allow low privileged users to read and modify registry settings related to control system functionality, allowing an authenticated attacker to cause system functions to stop or malfunction.
CVE-2019-19105 2 Abb, Busch-jaeger 4 Tg\/s3.2, Tg\/s3.2 Firmware, 6186\/11 and 1 more 2020-04-29 2.1 LOW 5.5 MEDIUM
The backup function in ABB Telephone Gateway TG/S 3.2 and Busch-Jaeger 6186/11 Telefon-Gateway saves the current settings and configuration of the application, including credentials of existing user accounts and other configuration's credentials in plaintext.
CVE-2019-10995 1 Abb 16 Cp651, Cp651-web, Cp651-web Firmware and 13 more 2020-01-24 5.8 MEDIUM 8.8 HIGH
ABB CP651 HMI products revision BSP UN30 v1.76 and prior implement hidden administrative accounts that are used during the provisioning phase of the HMI interface.
CVE-2019-18995 1 Abb 1 Pb610 Panel Builder 600 2019-12-31 5.0 MEDIUM 5.3 MEDIUM
The HMISimulator component of ABB PB610 Panel Builder 600 versions 2.8.0.424 and earlier fails to validate the content-length field for HTTP requests, exposing HMISimulator to denial of service via crafted HTTP requests manipulating the content-length setting.
CVE-2019-18994 1 Abb 1 Pb610 Panel Builder 600 2019-12-31 3.5 LOW 6.5 MEDIUM
Due to a lack of file length check, the HMIStudio component of ABB PB610 Panel Builder 600 versions 2.8.0.424 and earlier crashes when trying to load an empty *.JPR application file. An attacker with access to the file system might be able to cause application malfunction such as denial of service.