Filtered by vendor Rockwellautomation
Subscribe
Total
241 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2021-27475 | 1 Rockwellautomation | 1 Connected Components Workbench | 2022-03-29 | 6.8 MEDIUM | 8.6 HIGH |
| Rockwell Automation Connected Components Workbench v12.00.00 and prior does not limit the objects that can be deserialized. This vulnerability allows attackers to craft a malicious serialized object that, if opened by a local user in Connected Components Workbench, may result in remote code execution. This vulnerability requires user interaction to be successfully exploited. | |||||
| CVE-2021-27473 | 1 Rockwellautomation | 1 Connected Components Workbench | 2022-03-29 | 6.9 MEDIUM | 8.2 HIGH |
| Rockwell Automation Connected Components Workbench v12.00.00 and prior does not sanitize paths specified within the .ccwarc archive file during extraction. This type of vulnerability is also commonly referred to as a Zip Slip. A local, authenticated attacker can create a malicious .ccwarc archive file that, when opened by Connected Components Workbench, will allow the attacker to gain the privileges of the software. If the software is running at SYSTEM level, the attacker will gain admin level privileges. User interaction is required for this exploit to be successful. | |||||
| CVE-2021-27460 | 1 Rockwellautomation | 1 Factorytalk Assetcentre | 2022-03-29 | 7.5 HIGH | 9.8 CRITICAL |
| Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier components contain .NET remoting endpoints that deserialize untrusted data without sufficiently verifying that the resulting data will be valid. This vulnerability may allow a remote, unauthenticated attacker to gain full access to the FactoryTalk AssetCentre main server and all agent machines. | |||||
| CVE-2017-6024 | 1 Rockwellautomation | 4 Compactlogix 5380, Compactlogix 5380 Firmware, Controllogix 5580 and 1 more | 2022-03-23 | 7.1 HIGH | 5.9 MEDIUM |
| A Resource Exhaustion issue was discovered in Rockwell Automation ControlLogix 5580 controllers V28.011, V28.012, and V28.013; ControlLogix 5580 controllers V29.011; CompactLogix 5380 controllers V28.011; and CompactLogix 5380 controllers V29.011. This vulnerability may allow an attacker to cause a denial of service condition by sending a series of specific CIP-based commands to the controller. | |||||
| CVE-2020-14502 | 1 Rockwellautomation | 4 1734-aentr Point I\/o Dual Port Network Adaptor Series B, 1734-aentr Point I\/o Dual Port Network Adaptor Series B Firmware, 1734-aentr Point I\/o Dual Port Network Adaptor Series C and 1 more | 2022-03-07 | 4.3 MEDIUM | 6.1 MEDIUM |
| The web interface of the 1734-AENTR communication module is vulnerable to stored XSS. A remote, unauthenticated attacker could store a malicious script within the web interface that, when executed, could modify some string values on the homepage of the web interface. | |||||
| CVE-2020-14480 | 1 Rockwellautomation | 1 Factorytalk View | 2022-03-04 | 2.1 LOW | 5.5 MEDIUM |
| Due to usernames/passwords being stored in plaintext in Random Access Memory (RAM), a local, authenticated attacker could gain access to certain credentials, including Windows Logon credentials. | |||||
| CVE-2020-14481 | 1 Rockwellautomation | 1 Factorytalk View | 2022-03-04 | 2.1 LOW | 7.8 HIGH |
| The DeskLock tool provided with FactoryTalk View SE uses a weak encryption algorithm that may allow a local, authenticated attacker to decipher user credentials, including the Windows user or Windows DeskLock passwords. If the compromised user has an administrative account, an attacker could gain full access to the user’s operating system and certain components of FactoryTalk View SE. | |||||
| CVE-2020-14478 | 1 Rockwellautomation | 1 Factorytalk Services Platform | 2022-03-04 | 5.6 MEDIUM | 7.1 HIGH |
| A local, authenticated attacker could use an XML External Entity (XXE) attack to exploit weakly configured XML files to access local or remote content. A successful exploit could potentially cause a denial-of-service condition and allow the attacker to arbitrarily read any local file via system-level services. | |||||
| CVE-2016-9343 | 1 Rockwellautomation | 32 1768 Compact Guardlogix L4xs Controller, 1768 Compact Guardlogix L4xs Controller Firmware, 1768 Compactlogix L4x Controller and 29 more | 2022-02-03 | 7.5 HIGH | 10.0 CRITICAL |
| An issue was discovered in Rockwell Automation Logix5000 Programmable Automation Controller FRN 16.00 through 21.00 (excluding all firmware versions prior to FRN 16.00, which are not affected). By sending malformed common industrial protocol (CIP) packet, an attacker may be able to overflow a stack-based buffer and execute code on the controller or initiate a nonrecoverable fault resulting in a denial of service. | |||||
| CVE-2020-12029 | 1 Rockwellautomation | 1 Factorytalk View | 2022-01-04 | 6.8 MEDIUM | 7.8 HIGH |
| All versions of FactoryTalk View SE do not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE). Rockwell Automation recommends applying patch 1126289. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx. | |||||
| CVE-2020-12001 | 1 Rockwellautomation | 2 Factorytalk Linx, Rslinx Classic | 2021-11-04 | 7.5 HIGH | 9.8 CRITICAL |
| FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. The parsing mechanism that processes certain file types does not provide input sanitation. This may allow an attacker to use specially crafted files to traverse the file system and modify or expose sensitive data or execute arbitrary code. | |||||
| CVE-2019-13511 | 1 Rockwellautomation | 1 Arena Simulation Software | 2021-10-28 | 4.3 MEDIUM | 3.3 LOW |
| Rockwell Automation Arena Simulation Software versions 16.00.00 and earlier contain an INFORMATION EXPOSURE CWE-200. A maliciously crafted Arena file opened by an unsuspecting user may result in the limited exposure of information related to the targeted workstation. | |||||
| CVE-2020-12027 | 1 Rockwellautomation | 1 Factorytalk View | 2021-09-23 | 4.0 MEDIUM | 4.3 MEDIUM |
| All versions of FactoryTalk View SE disclose the hostnames and file paths for certain files within the system. A remote, authenticated attacker may be able to leverage this information for reconnaissance efforts. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs. | |||||
| CVE-2020-12031 | 1 Rockwellautomation | 1 Factorytalk View | 2021-09-23 | 4.6 MEDIUM | 7.8 HIGH |
| In all versions of FactoryTalk View SE, after bypassing memory corruption mechanisms found in the operating system, a local, authenticated attacker may corrupt the associated memory space allowing for arbitrary code execution. Rockwell Automation recommends applying patch 1126290. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx. | |||||
| CVE-2020-12038 | 1 Rockwellautomation | 5 Eds Subsystem, Rslinx, Rslinx Enterprise and 2 more | 2021-09-23 | 4.3 MEDIUM | 5.5 MEDIUM |
| Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable. A memory corruption vulnerability exists in the algorithm that matches square brackets in the EDS subsystem. This may allow an attacker to craft specialized EDS files to crash the EDSParser COM object, leading to denial-of-service conditions. | |||||
| CVE-2021-33012 | 1 Rockwellautomation | 2 Micrologix 1100, Micrologix 1100 Firmware | 2021-07-12 | 5.0 MEDIUM | 8.6 HIGH |
| Rockwell Automation MicroLogix 1100, all versions, allows a remote, unauthenticated attacker sending specially crafted commands to cause the PLC to fault when the controller is switched to RUN mode, which results in a denial-of-service condition. If successfully exploited, this vulnerability will cause the controller to fault whenever the controller is switched to RUN mode. | |||||
| CVE-2018-0163 | 2 Cisco, Rockwellautomation | 96 1120 Connected Grid Router, 1240 Connected Grid Router, 1905 Serial Integrated Services Router and 93 more | 2021-04-28 | 3.3 LOW | 6.5 MEDIUM |
| A vulnerability in the 802.1x multiple-authentication (multi-auth) feature of Cisco IOS Software could allow an unauthenticated, adjacent attacker to bypass the authentication phase on an 802.1x multi-auth port. The vulnerability is due to a logic change error introduced into the code. An attacker could exploit this vulnerability by trying to access an 802.1x multi-auth port after a successful supplicant has authenticated. An exploit could allow the attacker to bypass the 802.1x access controls and obtain access to the network. Cisco Bug IDs: CSCvg69701. | |||||
| CVE-2020-10642 | 1 Rockwellautomation | 1 Rslinx Classic | 2021-04-02 | 7.2 HIGH | 7.8 HIGH |
| In Rockwell Automation RSLinx Classic versions 4.11.00 and prior, an authenticated local attacker could modify a registry key, which could lead to the execution of malicious code using system privileges when opening RSLinx Classic. | |||||
| CVE-2021-22659 | 1 Rockwellautomation | 2 Micrologix 1400, Micrologix 1400 Firmware | 2021-03-31 | 7.5 HIGH | 8.6 HIGH |
| Rockwell Automation MicroLogix 1400 Version 21.6 and below may allow a remote unauthenticated attacker to send a specially crafted Modbus packet allowing the attacker to retrieve or modify random values in the register. If successfully exploited, this may lead to a buffer overflow resulting in a denial-of-service condition. The FAULT LED will flash RED and communications may be lost. Recovery from denial-of-service condition requires the fault to be cleared by the user. | |||||
| CVE-2020-14516 | 1 Rockwellautomation | 1 Factorytalk Services Platform | 2021-03-26 | 7.5 HIGH | 10.0 CRITICAL |
| In Rockwell Automation FactoryTalk Services Platform Versions 6.10.00 and 6.11.00, there is an issue with the implementation of the SHA-256 hashing algorithm with FactoryTalk Services Platform that prevents the user password from being hashed properly. | |||||